| Produkt | dt8p1 : please refer to product catalog/contact csr for more details | ||
| application in domestic and commercial area permitted | no | ||
| 10.2.7 inscriptions | meets the product standard's requirements. | ||
| supply frequency | 50/60 hz | ||
| frame size | fr9 | ||
| assigned motor current im at 400 v, 50 hz, 110% overload | 279 a | ||
| 10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
| 10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
| rated frequency - max | 66 hz | ||
| Schutzart | ip21 nema other |
||
| rated operational current (ie) at 150% overload | 245 a | ||
| 10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
| rated frequency - min | 45 hz | ||
| suitable for | branch circuits, (ul/csa) | ||
| rated control voltage (uc) | 24 v dc (external, max. 250 ma) | ||
| equipment heat dissipation, current-dependent pvid | 3300 w | ||
| radio interference class | c2, c3: depending on the motor cable length, the connected load, and ambient conditions. external radio interference suppression filters (optional) may be necessary. | ||
| product category | variable frequency drives | ||
| heat dissipation per pole, current-dependent pvid | 0 w | ||
| 10.3 degree of protection of assemblies | does not apply, since the entire switchgear needs to be evaluated. | ||
| 10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
| Einbaulage | vertical | ||
| 10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
| number of inputs (digital) | 6 (parameterizable, max. 30 v dc) | ||
| voltage rating - max | 480 vac | ||
| heat dissipation details | operation (with 150 % overload) | ||
| connection to smartwire-dt | no | ||
| Schaltfrequenz | 3.6 khz, 1 - 10 khz adjustable, fpwm, power section, main circuit | ||
| output frequency - max | 320 hz | ||
| communication interface | canopen®, optional lonworks, optional profibus-dp devicenet, optional modbus-tcp, optional bacnet/ip, optional bacnet ms/tp, optional ethercat, optional ethernet ip, optional modbus-rtu, optional profinet, optional |
||
| number of relay outputs | 2 (parameterizable, n/o, 8 a (24 v dc) / 8 a (250 v ac) / 0,4 a (125 v dc)) | ||
| protection | finger and back-of-hand proof, protection against direct contact (bgv a3, vbg4) | ||
| 10.8 connections for external conductors | is the panel builder's responsibility. | ||
| rated operational power at 380/400 v, 50 hz | 132 kw | ||
| fitted with: | radio interference suppression filter oled display dc link choke igbt inverter internal dc link |
||
| ambient storage temperature - min | -40 °c | ||
| 10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
| 10.4 clearances and creepage distances | meets the product standard's requirements. | ||
| assigned motor current im at 440/480 v, 60 hz, 110% overload | 302 a | ||
| 10.11 short-circuit rating | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
| mains voltage - max | 500 v | ||
| certifications | ul category control no.: nmms, nmms2, nmms7. nmms8 cul csa class no.: 3211-06 iec/en 61800-3 ul file no.: e134360 ul report applies to both us and canada specification for general requirements: iec/en 61800-2 dnv csa-c22.2 no. 14 safety: en 61800-5-1: 2003 ce rcm iec/en61800-3 iec/en61800-5 ul 508c certified by ul for use in canada ul rohs, iso 9001 |
||
| product width | 480 mm | ||
| product length/depth | 1150 mm |
| industrial valves | dt8p1-06-5-11-in13 | ||
| altitude | max. 1000 m above 1000 m with 1 % performance reduction per 100 m max. 3000 m |
||
| 10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
| 10.2.2 corrosion resistance | meets the product standard's requirements. | ||
| converter type | other | ||
| assigned motor current im at 400 v, 50 hz, 150% overload | 231 a | ||
| ambient operating temperature at 150% overload - min | -10 °c | ||
| ambient storage temperature - max | 70 °c | ||
| rated operational current (ie) at 110% overload | 300 a | ||
| 10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
| 10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
| number of outputs (digital) | 1 (parameterizable, 48 v dc/50 ma) | ||
| operating mode | optional: vector control with feedback (clv) sensorless vector control (slv) u/f control |
||
| number of outputs (analog) | 1 | ||
| heat dissipation capacity pdiss | 0 w | ||
| assigned motor power at 460/480 v, 60 hz, 110% overload | 250 hp | ||
| assigned motor power at 460/480 v, 60 hz | 200 hp | ||
| resolution | 0.01 hz (frequency resolution, setpoint value) | ||
| electromagnetic compatibility | 1st and 2nd environments (according to en 61800-3) | ||
| 10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
| 10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
| 10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
| rated control supply voltage | 10 v dc (us, max. 10 ma) | ||
| ambient operating temperature - min | -10 °c | ||
| 10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
| static heat dissipation, non-current-dependent pvs | 0 w | ||
| rated operational power at 380/400 v, 50 hz, 110% overload | 160 kw | ||
| output voltage (u2) | 500 v ac, 3-phase 400 v ac, 3-phase 480 v ac, 3-phase |
||
| climatic proofing | < 95 % relative humidity, no condensation, no corrosion, no dripping water | ||
| application in industrial area permitted | no | ||
| ambient operating temperature - max | 50 °c | ||
| ambient operating temperature at 150% overload - max | 50 °c | ||
| system configuration type | ac supply systems with earthed center point | ||
| output frequency - min | 0 hz | ||
| mains voltage - min | 380 v | ||
| 10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
| 10.12 electromagnetic compatibility | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
| rated operational voltage | 480 v ac, 3-phase 400 v ac, 3-phase 500 v ac, 3-phase |
||
| number of inputs (analog) | 2 (parameterizable, 0 - 10 v dc, 0/4 - 20 ma) | ||
| rated operational current for specified heat dissipation (in) | 245 a | ||
| assigned motor current im at 440 - 480 v, 60 hz, 150% overload | 240 a | ||
| Produktgewicht | 146 kg | ||
| product height | 362 mm | ||
| ean | 4015081232802 |