| ean | 4015081232789 | ||
| product height | 257 mm | ||
| Product weight | 35 kg | ||
| assigned motor current im at 440 - 480 v, 60 hz, 150% overload | 77 a | ||
| rated operational current for specified heat dissipation (in) | 87 a | ||
| number of inputs (analog) | 2 (parameterizable, 0 - 10 v dc, 0/4 - 20 ma) | ||
| rated operational voltage | 400 v ac, 3-phase 500 v ac, 3-phase 480 v ac, 3-phase |
||
| 10.12 electromagnetic compatibility | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
| 10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
| mains voltage - min | 380 v | ||
| output frequency - min | 0 hz | ||
| system configuration type | ac supply systems with earthed center point | ||
| ambient operating temperature at 150% overload - max | 50 °c | ||
| ambient operating temperature - max | 50 °c | ||
| application in industrial area permitted | no | ||
| climatic proofing | < 95 % relative humidity, no condensation, no corrosion, no dripping water | ||
| output voltage (u2) | 480 v ac, 3-phase 400 v ac, 3-phase 500 v ac, 3-phase |
||
| rated operational power at 380/400 v, 50 hz, 110% overload | 55 kw | ||
| static heat dissipation, non-current-dependent pvs | 0 w | ||
| 10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
| ambient operating temperature - min | -10 °c | ||
| rated control supply voltage | 10 v dc (us, max. 10 ma) | ||
| 10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
| 10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
| 10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
| electromagnetic compatibility | 1st and 2nd environments (according to en 61800-3) | ||
| resolution | 0.01 hz (frequency resolution, setpoint value) | ||
| assigned motor power at 460/480 v, 60 hz | 60 hp | ||
| assigned motor power at 460/480 v, 60 hz, 110% overload | 75 hp | ||
| heat dissipation capacity pdiss | 0 w | ||
| number of outputs (analog) | 1 | ||
| operating mode | sensorless vector control (slv) u/f control optional: vector control with feedback (clv) |
||
| number of outputs (digital) | 1 (parameterizable, 48 v dc/50 ma) | ||
| 10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
| 10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
| rated operational current (ie) at 110% overload | 105 a | ||
| ambient storage temperature - max | 70 °c | ||
| ambient operating temperature at 150% overload - min | -10 °c | ||
| assigned motor current im at 400 v, 50 hz, 150% overload | 81 a | ||
| converter type | other | ||
| 10.2.2 corrosion resistance | meets the product standard's requirements. | ||
| 10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
| altitude | above 1000 m with 1 % performance reduction per 100 m max. 3000 m max. 1000 m |
||
| industrial valves | dt8p1-10-65-11-in13 |
| product length/depth | 640 mm | ||
| product width | 237 mm | ||
| certifications | certified by ul for use in canada rcm ce dnv iec/en61800-3 ul ul report applies to both us and canada csa class no.: 3211-06 specification for general requirements: iec/en 61800-2 csa-c22.2 no. 14 ul 508c cul rohs, iso 9001 iec/en 61800-3 safety: en 61800-5-1: 2003 iec/en61800-5 ul category control no.: nmms, nmms2, nmms7. nmms8 ul file no.: e134360 |
||
| mains voltage - max | 500 v | ||
| 10.11 short-circuit rating | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
| assigned motor current im at 440/480 v, 60 hz, 110% overload | 96 a | ||
| 10.4 clearances and creepage distances | meets the product standard's requirements. | ||
| 10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
| ambient storage temperature - min | -40 °c | ||
| fitted with: | igbt inverter radio interference suppression filter oled display dc link choke internal dc link |
||
| rated operational power at 380/400 v, 50 hz | 45 kw | ||
| 10.8 connections for external conductors | is the panel builder's responsibility. | ||
| protection | finger and back-of-hand proof, protection against direct contact (bgv a3, vbg4) | ||
| number of relay outputs | 2 (parameterizable, n/o, 8 a (24 v dc) / 8 a (250 v ac) / 0,4 a (125 v dc)) | ||
| communication interface | lonworks, optional modbus-tcp, optional profibus-dp bacnet/ip, optional devicenet, optional canopen®, optional bacnet ms/tp, optional ethercat, optional ethernet ip, optional modbus-rtu, optional profinet, optional |
||
| output frequency - max | 320 hz | ||
| switching frequency | 3.6 khz, 1 - 10 khz adjustable, fpwm, power section, main circuit | ||
| connection to smartwire-dt | no | ||
| heat dissipation details | operation (with 150 % overload) | ||
| voltage rating - max | 480 vac | ||
| number of inputs (digital) | 6 (parameterizable, max. 30 v dc) | ||
| 10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
| Mounting position | vertical | ||
| 10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
| 10.3 degree of protection of assemblies | does not apply, since the entire switchgear needs to be evaluated. | ||
| heat dissipation per pole, current-dependent pvid | 0 w | ||
| product category | variable frequency drives | ||
| radio interference class | c2, c3: depending on the motor cable length, the connected load, and ambient conditions. external radio interference suppression filters (optional) may be necessary. | ||
| equipment heat dissipation, current-dependent pvid | 1125 w | ||
| rated control voltage (uc) | 24 v dc (external, max. 250 ma) | ||
| suitable for | branch circuits, (ul/csa) | ||
| rated frequency - min | 45 hz | ||
| 10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
| rated operational current (ie) at 150% overload | 87 a | ||
| Degree of protection | ip21 nema other |
||
| rated frequency - max | 66 hz | ||
| 10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
| 10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
| assigned motor current im at 400 v, 50 hz, 110% overload | 99 a | ||
| frame size | fr7 | ||
| supply frequency | 50/60 hz | ||
| 10.2.7 inscriptions | meets the product standard's requirements. | ||
| application in domestic and commercial area permitted | no | ||
| product | dt8p1 : please refer to product catalog/contact csr for more details |
| Stock | 1 pcs. |
|---|---|
| Part number | 125668 |
| Manufacturer | VICKERS |
| Quantity | Unit Price |
|---|---|
| 1+ | 349.08 € |
Cookies are small text files that can enhance a user's experience on websites
The law stipulates that we can store strictly necessary cookies on your device for the proper functioning of this site. For other types of cookies, we require your permission. This means necessary cookies are processed under GDPR Art. 6 (1) (f), while all other cookies, such as those in the preferences and marketing categories, are processed under GDPR Art. 6 (1) (a) GDPR.
cookies.cookies_about_type
You have the option to change or withdraw your consent at any time through the Cookie Declaration on our website.
Find more information about our identity, how to contact us, and our personal data processing practices in our Privacy Policy.