| rated insulation voltage (ui) | 440 v | ||
| rated fault current - min | .1 a | ||
| permitted storage and transport temperature - max | 60 °c | ||
| 10.2.7 inscriptions | meets the product standard's requirements. | ||
| 10.2.2 corrosion resistance | meets the product standard's requirements. | ||
| connectable conductor cross section (multi-wired) - max | 16 mm² | ||
| rated impulse withstand voltage (uimp) | 4 kv | ||
| 10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
| accessories required | z-hk 248432 | ||
| Degree of protection | ip20, ip40 with suitable enclosure ip20 |
||
| 10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
| lifespan, mechanical | 20000 operations | ||
| 10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
| width in number of modular spacings | 4 | ||
| heat dissipation capacity | 0 w | ||
| built-in width (number of units) | 70 mm (4 su) | ||
| leakage current type | ac | ||
| voltage type | ac | ||
| Application | residual current circuit breaker for residential and commercial applications xpole - switchgear for residential and commercial applications |
||
| 10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
| 10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
| used with | klv-tc-4 276241 (compact enclosure) z-fw/lp 248296 (remote control and automatic switching device) z-rc/ak-4te 101062 (sealing cover set) residual current circuit breakers pf7 type ac |
||
| rated short-circuit strength | 10 ka | ||
| ambient operating temperature - min | -25 °c | ||
| number of poles | four-pole | ||
| connectable conductor cross section (solid-core) - min | 1.5 mm² | ||
| Features | residual current circuit breaker additional equipment possible |
||
| built-in depth | 69.5 mm | ||
| heat dissipation per pole, current-dependent | 0 w | ||
| sensitivity type | ac current sensitive | ||
| terminal protection | finger and hand touch safe, dguv vs3, en 50274 | ||
| 10.8 connections for external conductors | is the panel builder's responsibility. | ||
| rated residual making and breaking capacity | 500 a | ||
| tripping time | non-delayed | ||
| test circuit range | 184 v ac - 440 v ac | ||
| 10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
| mounting method | din rail quick attachment with 2 latch positions for din-rail iec/en 60715 |
||
| 10.4 clearances and creepage distances | meets the product standard's requirements. | ||
| 10.11 short-circuit rating | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
| certifications | iec/en 61008 | ||
| Product weight | .32 kg | ||
| product height | 71 mm | ||
| ean | 4015082635855 |
| rated operational voltage (ue) - max | 400 v | ||
| admissible back-up fuse overload - max | 25 a gg/gl | ||
| surge current capacity | .25 ka | ||
| 10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
| Type | pf7 residual current circuit breakers type ac |
||
| 10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
| connectable conductor cross section (multi-wired) - min | 1.5 mm² | ||
| Pollution degree | 2 | ||
| rated short-time withstand current (icw) | 10 ka | ||
| connectable conductor cross section (solid-core) - max | 35 mm² | ||
| voltage rating | 230 v ac / 400 v ac | ||
| 10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
| busbar material thickness | 0.8 mm - 2 mm | ||
| impulse withstand current | partly surge-proof 250 a | ||
| terminals (top and bottom) | open mouthed/lift terminals | ||
| frame | 45 mm | ||
| terminal capacity (stranded cable) | 16 mm² (2x) | ||
| 10.3 degree of protection of assemblies | does not apply, since the entire switchgear needs to be evaluated. | ||
| static heat dissipation, non-current-dependent | 0 w | ||
| 10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
| equipment heat dissipation, current-dependent | 2.8 w | ||
| 10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
| 10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
| terminal capacity (solid wire) | 1.5 mm² - 35 mm² | ||
| 10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
| lifespan, electrical | 4000 operations | ||
| short-circuit rating | 63 a (max. admissible back-up fuse) | ||
| climatic proofing | 25-55 °c / 90-95% relative humidity according to iec 60068-2 | ||
| ambient operating temperature - max | 55 °c | ||
| special features | maximum operating temperature is 55 °c: starting at 40 °c, the max. permissible continuous current decreases by 3% for every 1 °c tripping signal contact for subsequent installation z-nhk 248434 |
||
| fault current rating | 100 ma | ||
| frequency rating | 50 hz | ||
| fitted with: | is/spe-1te 101911 interlocking device |
||
| 10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
| rated fault current - max | .1 a | ||
| amperage rating | 25 a | ||
| 10.12 electromagnetic compatibility | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
| permitted storage and transport temperature - min | -35 °c | ||
| rated operational current for specified heat dissipation (in) | 25 a | ||
| compliances | rohs conform | ||
| product width | 70 mm | ||
| product length/depth | 80 mm |