| Number of high-speed logic inputs | 2 | ||
| Number of safe 2-pin inputs | 2 | ||
| SFF Safe Failure Fraction | 99 % | ||
| Performance Level (PL) | Safe brake control (SBC)/category 3, performance level e Safe Torque Off (STO)/category 4, performance level e | ||
| Safety function | Safe brake control (SBC) Safe torque off (STO) Safe Stop 1 (SS1) | ||
| Working range of analogue inputs | ± 10 V | ||
| Features of setpoint inputs | Differential inputs Configurable for speed Configurable for current/force | ||
| Max. current of the floating switching outputs | 50 mA | ||
| Time resolution of high-speed switching outputs | 1 µs | ||
| Max. current digital logic outputs | 20 mA | ||
| Switching logic for outputs | PNP (positive switching) | ||
| Time resolution of high-speed logic inputs | 1 µs | ||
| Specification logic input | Based on IEC 61131-2, type 3 | ||
| Switching logic for inputs | PNP (positive switching) | ||
| KC mark | KC-EMV | ||
| Based on standard | EN 50581 EN 60204-1 EN 61508-1 EN 61508-2 EN 61508-3 EN 61508-4 EN 61508-5 EN 61508-6 EN 61508-7 EN 61800-2 EN 62061 | ||
| Operator controls | Optional: CDSB operator unit | ||
| Product weight | 2.100 g | ||
| Type of mounting | Mounting plate, attached with screws | ||
| Number of digital logic inputs | 12 | ||
| Encoder interface output, features | 1 MHz maximum output frequency Max. 16384 ppr | ||
| Encoder interface 2, function | Incremental encoder SIN/COS encoder | ||
| Field bus, connection system | RJ45 | ||
| Field bus interface, transmission rate | 100 Mbit/s | ||
| Communication profile | DriveProfile | ||
| Fieldbus interface, function | Bus connection incoming/outgoing EtherNet/IP slave | ||
| Ethernet interface, protocol | TCP/IP | ||
| Controller operating mode | Cascade controller P position controller PI speed controller PI current regulator for F or M Profile operation with record and direct mode Interpolated mode via fieldbus Synchronised operating modes Homing Setting-up Autotuning | ||
| Max. voltage drop from logic supply to brake output | 0,8 V | ||
| Max. length of motor cable without external mains filter | 50 m | ||
| Maximum output | 3.600 VA | ||
| Max. peak current duration | 2 s | ||
| Nominal current per phase, effective | 2,5 A | ||
| Max. current consumption, logic power supply with clamping brake and I/O | 2,3 A | ||
| Current consumption of logic power supply without clamping brake | 0,5 A | ||
| Nominal voltage for logic power supply DC | 24 V | ||
| Brake resistor, external | 130 Ohm ... 250 Ohm | ||
| Pulse energy for braking resistor | 850 Ws | ||
| Brake resistor, integrated | 130 Ohm | ||
| Permissible range for load power supply | ± 10 % | ||
| Mains types | TN IT | ||
| System voltage to EN 61800-5-1 | 300 V | ||
| Active PFC | no | ||
| Nominal current, load supply | 3 A | ||
| Input voltage range AC | 200 V ... 480 V | ||
| Nominal operating voltage AC | 400 V | ||
| LABS (PWIS) conformity | VDMA24364 zone III | ||
| Immunity to surge | 6 kV | ||
| Overvoltage category | III | ||
| Degree of protection | IP20 | ||
| Max. installation height | 2.000 m | ||
| UL ambient temperature | 0 °C ... 40 °C | ||
| Ambient temperature | 0 °C ... 50 °C | ||
| Certificate issuing authority | German Technical Control Board (TÜV) Rheinland 01/205/5640.00/18 TÜV Rheinland UK Ltd. 01/205U/5640.00/22 UL E331130 |
| Number of diagnostic outputs | 2 | ||
| Hardware fault tolerance | 1 | ||
| Diagnostic coverage | 97 % | ||
| Safety Integrity Level (SIL) | Safe brake control (SBC)/SIL 3/SILCL 3 Safe torque off (STO)/SIL 3/SILCL 3 | ||
| Impedance of setpoint input | 70 kOhm | ||
| Working range setpoint input | ± 10 V | ||
| Number of analogue setpoint inputs | 1 | ||
| Number of floating switching outputs | 1 | ||
| Number of high-speed switching outputs | 2 | ||
| Features of digital logic outputs | Freely configurable in some cases Not galvanically isolated Diagnostics outputs in some cases | ||
| Number of digital logic outputs 24 V DC | 6 | ||
| Working range of logic input | -3 V ... 30 V | ||
| Features of logic input | Freely configurable in some cases Safety inputs in some cases Not galvanically isolated | ||
| CE mark (see declaration of conformity) | To EU EMC Directive To EC Machinery Directive In accordance with EU RoHS Directive | ||
| Approval | RCM trademark German Technical Control Board (TÜV) c UL us listed (OL) | ||
| Conforms to standard | EN 61800-3 EN 61800-5-1 EN 61800-5-2 EN ISO 13849-1 | ||
| Display | Green/yellow/red LED | ||
| Mounting position | Free convection Vertical | ||
| Operating mode of drive unit | Field-oriented closed-loop control Position resolution 24 bit/rev Sampling rate 16 kHz PWM at 8 or 16 KHz Vector modulation with 3rd harmonic Real-time data acquisition 2x input capture (x, v, F) 2x output trigger (x, v, F) 2x position encoder input 1x SYNC interface for encoder emulation or encoder input | ||
| Encoder interface input, features | 1 MHz maximum output frequency Max. 16384 ppr | ||
| Synchronisation interface, function | Encoder emulation A/B/Z Encoder input A/B/Z | ||
| Encoder interface, function | ENDAT® 2.1 encoder EnDat® 2.2 encoder Hiperface-Geber Incremental encoder Nikon SIN/COS encoder | ||
| Field bus, connection type | 2x socket | ||
| Process interfacing | Adjustable-speed drives Drives with positioning function | ||
| Fieldbus link | EtherNet/IP Modbus/TCP | ||
| Field bus, protocol | EtherNet/IP Modbus/TCP | ||
| Ethernet interface, function | Parameterisation and commissioning | ||
| Number of inputs for motor temperature sensor | 1 | ||
| Max. output current of holding brake | 1 A | ||
| Output frequency | 0 Hz ... 599 Hz | ||
| Controller nominal output | 1.200 VA | ||
| Peak current per phase, effective | 7,5 A | ||
| Output voltage class AC | 3x (0 – input) V | ||
| Current consumption for logic supply with parking brake | 1,5 A | ||
| Permissible range for logic voltage | ± 20 % | ||
| Max. continuous output of the external braking resistor (IEC) | 600 W | ||
| Nominal power braking resistor (IEC) | 48 W | ||
| Pulse power, brake resistance | 5 kVA | ||
| Max. intermediate circuit voltage DC | 800 V | ||
| Nominal voltage load voltage DC | 560 V | ||
| Max. short circuit current rating of the mains | 10 kA | ||
| Mains filter | Integrated | ||
| Peak current load power supply | 9 A | ||
| Mains frequency | 48 Hz ... 62 Hz | ||
| Permissible voltage fluctuations | +/- 10 % | ||
| Phases of nominal operating voltage | 3-phase | ||
| Note on materials | RoHS-compliant | ||
| Pollution degree | 2 | ||
| Protection class | I | ||
| Note on max. installation height | From 1000 m: power reduction by 1% per 100 m. | ||
| Relative air humidity | 5 - 90% Non-condensing | ||
| Note on ambient temperature | Power must be reduced by 3% per °C at ambient temperatures above 40°C. | ||
| Storage temperature | -25 °C ... 55 °C | ||
| CE marking (see declaration of conformity) | To UK instructions for EMC To UK regulations for machines To UK RoHS instructions |
| Stock | Ask for quotation |
|---|---|
| Part number | 5340827 |
| Manufacturer | FESTO |
| Quantity | Unit Price |
|---|---|
| 1+ | 1,610.75 € |
Cookies are small text files that can enhance a user's experience on websites
The law stipulates that we can store strictly necessary cookies on your device for the proper functioning of this site. For other types of cookies, we require your permission. This means necessary cookies are processed under GDPR Art. 6 (1) (f), while all other cookies, such as those in the preferences and marketing categories, are processed under GDPR Art. 6 (1) (a) GDPR.
cookies.cookies_about_type
You have the option to change or withdraw your consent at any time through the Cookie Declaration on our website.
Find more information about our identity, how to contact us, and our personal data processing practices in our Privacy Policy.